Abstract
This paper investigates detecting patterns in the pressure signal of a compressed air system (CAS) with a load/unload control using a wavelet transform. The pressure signal of a CAS carries useful information about operational events. These events form patterns that can be used as ‘signatures’ for event detection. Such patterns are not always apparent in the time domain and hence the signal was transformed to the time-frequency domain. Three different CAS operating modes were considered: idle, tool activation and faulty. The wavelet transforms of the CAS pressure signal reveal unique features to identify events within each mode. Future work will investigate creating machine learning tools for that utilize these features for fault detection in CAS.
You have full access to this open access chapter, Download conference paper PDF
Similar content being viewed by others
Keywords
1 Introduction and Literature Review
This paper investigates detection of patterns in CAS pressure signal using a continuous wavelet transform (WT). CAS pressure signal characteristics that make WT a suitable analysis tool are discussed. Then, experiments performed and results obtained after applying WT are presented. Matlab function ‘cwt’ was used to apply WT. Results confirm that applying WT on a CAS pressure signal reveals unique patterns that can be used for fault detection.
Running a Compressed Air System (CAS) has a high energy cost [1, 2] and the efficiency of many CAS could be improved. Innovations in intelligent systems for automatic energy consumption control and fault detection might help address CAS energy efficiency [3].
Section 8.2 considers the CAS pressure signal, Sect. 8.3 presents the experiment and results and Sect. 8.4 concludes the paper.
2 Compressed Air Pressure Signal
A CAS pressure signal contains patterns that may be associated with operational events. Events, such as a compressor turning on or off in system with load/unload control, could be detected directly from the time domain pressure signal. However, detecting other events, such as tool or filter activation, was not as straightforward. In such cases, transforming the pressure signal to the frequency domain revealed features to recognise these events. The CAS pressure signal is non-stationary. For non-stationary signals, a Fourier transform provides information about frequency content, but not about time localization of those frequencies. A time-frequency signal processing tool, such as the WT, is more suitable for analysing a load/unload CAS pressure signal. A similar attempt to analyse a CAS pressure signal with WT was investigated in [4].
3 Experiments and Results
The industrial CAS installed in the University of Portsmouth was used for data collection. A pressure sensor was connected to the piping network and an air gun was used to simulate a tool activation. Data was recorded at a rate of 1 sample per second. The compressor had load/unload control, so the compressor turned on when the tank reached the lowest pressure limit and off when it reached the upper pressure limit. Three different scenarios were considered. The first corresponded to the case where no tool was activated (referred to as idle case). In the second case, an air gun was activated to simulate a tool activation. Finally, the third case corresponded to data recorded when the system had a leaking filter and different compressor control pressure limits. Each of these cases are analysed.
3.1 Idle Case
In the idle case compressed air consumption was due to small leaks in the system. Figure 8.1 shows pressure variation in this case. Pressure variation was obtained by removing the mean from the recorded data. The compressor switched on when the system pressure decreased by ~0.15 bar leading to a rapid increase in system pressure. Once the compressor switched off, the pressure decreased slowly. While the compressor was off, events such as filter activation, led to an increased loss in system pressure, reflected as a steeper decrease in pressure.
The WT of the idle signal is shown as a 3D contour plot in Fig. 8.2. On the z-axis, coefficient magnitude instead of coefficient are plotted to make visualization easier. Low frequency components (~0.01 Hz) had the highest coefficient magnitude and were present at all times. These components corresponded to the overall saw tooth pattern of the signal (period of 100 s and frequency of 0.01 Hz). Compressor switching on introduced higher frequency components identifiable on the WT plot. These components had peaks (of different magnitudes) at frequencies of 0.05 and 0.25 Hz, both disappearing after the compressor switched off. Filter activation generated patterns with a peak at a frequency of 0.05 Hz.
3.2 Tool Activation Case
An air gun was used to study the impact of a tool activation. Compared to the idle case tool activation, while the compressor was on, led to longer compressor running times before the upper pressure limit was reached. Tool activation while the compressor was off increased the rate of air discharge, which accelerated pressure decrease so that the system reached the lower pressure limit faster. Figures 8.3 shows a pressure change while the air gun was on.
The WT of the tool activation signal is shown in Fig. 8.4. The plot reveals two patterns of interest. The first is the coefficients at frequencies of 0.05 Hz, and the second pattern is the coefficients at frequency range of 0.1–0.2 Hz. Both of these patterns were present at almost all times, unlike the idle case in which these frequencies only appeared when the compressor was on or when a filter was activated. While the tool was activated, compressor charging and discharging in the time domain signal had relatively similar slopes. This led to similar frequency components being present at all times.
3.3 Faulty Case
Data recorded when the system had two different faults was utilized to analyse faulty behaviour using a wavelet transform. The systems pressure control limits deviated from original settings, pushing the upper pressure limit higher. In addition, one of the filters had a relatively large leak. The pressure change for this case is shown in Fig. 8.5 alongside the idle case for comparison.
Because the upper pressure limit was higher, and due to the leak in the filter, the time the compressor spent on was longer. Moreover, the increased compressed air consumption due to the leak, meant the lower pressure limit was reached faster. The WT of the faulty system signal is shown in Fig. 8.6. Because the amplitude of the signal was relatively high (compared to idle and tool activation cases), the magnitude of the low frequency components was also high (0.14 compared to 0.025 and 0.1 in the idle and tool activation cases). The high frequency spectral components were similar to the ones seen for the tool activation case. This result is expected since a tool activation, such as an air gun, resembles the presence of a leak in the system.
4 Conclusion
This paper investigated the suitability of the WT for extracting features from the pressure signal of a CAS. Three different cases were considered: Idle, faulty and tool activation. The analysis proved that it is possible to generate features to identify different events, such as a tool activation and leaks. Future work will investigate employing those features to create a classifier for leak detection.
References
Fridén H, Bergfors L, Björk A, Mazharsolook E, Energy and LCC optimised design of compressed air systems: a mixed integer optimisation approach with general applicability. Proceedings-2012 14th International Conference on Modelling and Simulatio (2012), pp. 491–496
Murphy S, Kissock K, Simulating energy efficient control of multiple-compressor compressed air systems. Proceedings of Industrial Energy Technology Conference (2015)
M. Benedetti, V. Cesarotti, V. Introna, J. Serranti, Energy consumption control automation using artificial neural networks and adaptive algorithms: proposal of a new methodology and case study. Appl. Energy 165, 60–71 (2016)
Desmet A, Delore M, Leak detection in compressed air systems using unsupervised anomaly detection techniques. Proceedings of Annual Conference of the Prognostics and Health Management Society PHM (2017), pp. 211–220
Acknowledgements
The research was supported by the DTA3/COFUND Marie Skłodowska-Curie PhD Fellowship programme partly funded by the Horizon 2020 European Programme.
Author information
Authors and Affiliations
Corresponding author
Editor information
Editors and Affiliations
Rights and permissions
Open Access This chapter is licensed under the terms of the Creative Commons Attribution 4.0 International License (http://creativecommons.org/licenses/by/4.0/), which permits use, sharing, adaptation, distribution and reproduction in any medium or format, as long as you give appropriate credit to the original author(s) and the source, provide a link to the Creative Commons license and indicate if changes were made.
The images or other third party material in this chapter are included in the chapter's Creative Commons license, unless indicated otherwise in a credit line to the material. If material is not included in the chapter's Creative Commons license and your intended use is not permitted by statutory regulation or exceeds the permitted use, you will need to obtain permission directly from the copyright holder.
Copyright information
© 2021 The Author(s)
About this paper
Cite this paper
Thabet, M., Sanders, D., Bausch, N. (2021). Detection of Patterns in Pressure Signal of Compressed Air System Using Wavelet Transform. In: Mporas, I., Kourtessis, P., Al-Habaibeh, A., Asthana, A., Vukovic, V., Senior, J. (eds) Energy and Sustainable Futures. Springer Proceedings in Energy. Springer, Cham. https://doi.org/10.1007/978-3-030-63916-7_8
Download citation
DOI: https://doi.org/10.1007/978-3-030-63916-7_8
Published:
Publisher Name: Springer, Cham
Print ISBN: 978-3-030-63915-0
Online ISBN: 978-3-030-63916-7
eBook Packages: EnergyEnergy (R0)